Model, FID PRO, low-resistance cut-off dampers are designed for use in comfort ventilation installation, in points of penetration of these installations through vertical and horizontal building partitions. They are installed in systems with increased acoustic requirements. During fire, they allow to maintain fire resistance of the building partition through which ventilation and air conditioning ducts run. They also prevent propagation of fire, smoke and fire gases to the safe part of the building.
When made for potentially explosive zones (EX variant), the dampers may operate in zone 1 (risk of explosion of gases inside and outside of ventilation ducts) and zone 21 (risk of explosion of dust outside ducts). The dampers conform to the requirements of group II category 2G and -/2D.
FEATURES
- Low flow resistance
- Nipple or muff variant
- Installation in walls and ceilings
- Optional making in EX variant
- Operating reliability up to 10000 cycles
DIMENSIONS
NOMINAL WIDTH (Ø) | From 100-315 mm |
*Apart from standard dimensions, dampers can be costumized to any size withing the specified ranges. |
CONTROLS
RST MECHANISM | - Thermal trigger 72°C (optionally 95°C) on partition - Actuating spring - Manual arming |
RST/WK1 MECHANISM | - Thermal trigger 74°C (optionally 95°C) on partition - Actuating spring - Limit switch - Manual arming |
RST-KW1/S INTEGRATED MECHANISM | - Thermal trigger 74°C (optionally 95°C) in the mechanism - Actuating spring - Manual arming |
RST-KW1/WK1 or WK2 MECHANISM - INTEGRATED MECHANISM | - Thermal trigger 74°C (optionally 95°C) in the mechanism - Actuating spring - One or two limit switch(es) - Manual arming |
RST/KW1/24L MECHANISM - INTEGRATED MECHANISM | - Thermal trigger 74°C (optionally 95°C) in the mechanism - Actuating spring - One of two limit switch(es) - Electromagnetic trigger responding to current impulse - U=24V DC manual arming |
RST/KW1/24P MECHANISM | - Integrated mechanism (thermal trigger 74°C (optionally 95°C)) in the mechanism - Actuating spring - One or two limit switch(es) - Electromagnetic trigger responding to power decay - U=24V DC manual arming |
BELIMO TYPE MECHANISM | - Actuator series with return spring and thermoelectric trigger (BFL, BFN, EXBF series) |