Model, FID S/S c/P, low-resistance cut-off dampers are designed for use in general ventilation installations, in points of penetration of these installations through vertical and horizontal building partitions. The dampers are used, among others, for installations with increased acoustic requirements. During fire, they allow to maintain fire resistance of the building partition through which ventilation and air conditioning ducts run. They also prevent propagation of fire, smoke and fire gases to the safe part of the building.
When made for potentially explosive zones (EX variant), the dampers may operate in zone 1 (risk of explosion of gases inside and outside of ventilation ducts) and zone 21 (risk of explosion of dust outside ducts). The dampers conform to the requirements of group II category 2G and -/2D.
FEATURES
- Reduced hydralic
- Bracing-reinforced damper barrier - increased mechanical
- Installation in walls and ceilings
- Optional making in EX
- Operating reliability up to 10000 cycles
DIMENSIONS
NOMINAL WIDTH (Ø) | From 200-1000 mm |
NOMINAL HEIGHT | From 200-800 mm |
MAXIMUM AREA OF SECTION OF SINGLE DAMPER | Not larger than 0.8m² |
*Apart from standard dimensions, dampers can be costumized to any size withing the specified ranges. |
CONTROLS
RST MECHANISM | - Thermal trigger 72°C (optionally 95°C) on partition - Actuating spring - Manual arming |
RST/WK1 MECHANISM | - Thermal trigger 74°C (optionally 95°C) on partition - Actuating spring - Limit switch - Manual arming |
RST-KW1/S INTEGRATED MECHANISM | - Thermal trigger 74°C (optionally 95°C) in the mechanism - Actuating spring - Manual arming |
RST-KW1/WK1 OR WK2 MECHANISM - INTEGRATED MECHANISM | - Thermal trigger 74°C (optionally 95°C) in the mechanism - Actuating spring - One or two limit switch(es) - Manual arming |
RST/KW1/24L MECHANISM - INTEGRATED MECHANISM | - Thermal trigger 74°C (optionally 95°C) in the mechanism - Actuating spring - One of two limit switch(es) - Electromagnetic trigger responding to current impulse - U=24V DC manual arming |
RST/KW1/24P MECHANISM | - Integrated mechanism (thermal trigger 74°C (optionally 95°C)) in the mechanism - Actuating spring - One or two limit switch(es) - Electromagnetic trigger responding to power decay - U=24V DC manual arming |
BELIMO TYPE MECHANISM | - Actuator series with return spring and thermoelectric trigger (BFL, BFN, EXBF series) |
OPERATION AND MAINTENANCE MANUAL
View the Operation and maintenance manual for the single blade low resistance cut-off fire damper for comfort ventilation, model S/S c/P (Opens in new browser tab).
TECHNICAL CATALOGUE
View the technical catalogue for the single blade low resistance cut-off fire damper for comfort ventilation, model S/S c/P (Opens in new browser tab).